Supply Water Leak Monitoring and Alarm System NL-LSBJ-8/16 8 or 16 Channel Host Detectors Sounder Phone Alert

相关推荐

The problem

Nobody watches the plant room at night - by morning the floor is flooded and equipment is burnt; a single-point water rope covers little area, and an alarm that only sounds on site is useless when no one is there.

Capability

Water leak monitoring system made of an alarm host, leak sensing detectors, a sounder beacon and network notification. The host takes 8 or 16 detectors on a 4-core daisy chain, drives one sounder over 2 cores and shows the alarm loop number on an LED display; alarms also push to a mobile phone. Detector: DC12V water sensor in a fully potted die-cast zinc housing, 47x30x30mm, 1.5mm alarm height, 0.031W standby and 0.21W in alarm, normally-open (alarm on water) or normally-closed (alarm on water loss) versions, dry contact relay output; 1m AVVR 5x0.3mm2 cable as standard, M3x12 screws at 41mm pitch; -10 to 60C and 20-95 percent RH non-condensing. The system runs stand-alone or feeds a BMS, PLC or SCADA through dry contacts for centralized monitoring and drain pump interlock.

Key specifications

  • Application: water leak detection and alarm in machine rooms, switch rooms, pump rooms and laboratories
  • Capacity: 8 or 16 detector channels (4-core daisy chain wiring)
  • Alarm output: one sounder beacon (2-core) plus mobile phone notification
  • Host display: LED loop number display with per-loop status indication
  • Detector: DC12V water sensor, fully potted die-cast zinc housing
  • Sensitivity: 1.5mm alarm height; 0.031W standby, 0.21W in alarm
  • Size and fixing: 47 x 30 x 30mm; M3x12 screws at 41mm pitch
  • Cable: AVVR 5x0.3mm2, 1m standard; 4 cores to detectors, 2 cores to sounder
  • Contact form: normally open (alarm on water) or normally closed (alarm on water loss), dry contact
  • Environment: -10 to 60C, 20-95 percent RH non-condensing
  • Integration: dry contacts into BMS, PLC or SCADA for centralized monitoring and drain pump interlock

Applications

Machine rooms and switch rooms; water treatment and purifier plant rooms; laboratory sinks and wash areas; apartments, property plant floors, sumps and fire pump rooms

About the manufacturer

Guangdong Endurance Electronic Equipment Co., Ltd provides non-standard customization, drawing confirmation, factory acceptance, on-site installation and commissioning, operation training and lifetime technical service; 12-month warranty and lifetime spare parts supply. Tel: 0760-88500902 / 13416787649. Web: en.zsnaili.com.